Tunnel Liner

Composition

Our rigid fire protection panels are manufactured from layers of fibre reinforced magnesium and other refractory products. They can be left as a stand alone finish or can be painted if required, and they do not contain hazardous substances.

Available Thicknesses

  • 20mm
  • 24mm
  • 30mm

Tests

Dependant upon Thickness
RWS 1350 Certified 180 mins
HCM Certified 180 mins
ISO 834 Certified 240 mins

Fire Reaction

This product is classified as A1 (non combustible) according to European Standard EN 13501-1 and British Standard BS 476: Part 4.


El 180 - Tunnel Post Fixed Application (30 mm)

Tests

Standard: RWS Fire Curve and HCM.

Solution

  1. 30 mm boards.
  2. Concrete slab.
  3. Min. M6x85 A4 316 metal anchor.

El 240 - Tunnel Post Fixed Application (30 mm)

Tests

Standard: ISO 834.

Solution

  1. 30 mm boards.
  2. Concrete slab.
  3. Min. M6x85 A4 316 metal anchor.

El 120 - Tunnel Post Fixed Application (24 mm)

Tests

Standard: RWS Fire Curve.

Solution

  1. 24 mm boards.
  2. Concrete slab.
  3. Min. M6x85 A4 316 metal anchor.

El 120 - Tunnel Lost Formwork Application (30 mm)

Tests

Standard: RWS Fire Curve.

Solution

  1. 30 mm boards.
  2. Concrete slab.
  3. IDMR SS 316 80 mm or Fischer DHM 30 – 80 mm A4 316 Duplex metal anchor.

Product Format, Transport and Storage

PassiveTec® Tunnel Liner boards are packed in secured edge-protected pallets and are identified with a sticker indicating: product name, production date, pallet number, and number of boards per pallet. All boards are stamped with production date.

PassiveTec® boards must be stored in their original pallets as delivered from the factory, under cover, not exposed to rain and in a dry place, and when removed from the pallet, they should be kept in an upright position.

PassiveTec® Physical Properties
Fire performance non combustible A1 class
Density 950 kg/m3 ± 10 %
Thermal conductivity (W/m.K) 0,29
Thermal resistance (m2.K/W) 0,1
Lineal thermal expansion a (°K-1) - 3,1 x 10-5 (long) and - 4,1 x 10-5 (tran)
Electrical surface resistance [kΩ] 5,1
Bending strength. Modulus of rupture MORa (N/mm2) 4,7
Tensile strength parallel to faces: σ (kPa) 931
Tensile strength perpendicular to faces: σ (kPa)  1550
Determination of compression behavior. Breaking load (N) 25213
Lengthwise tolerance ± 2 mm
Widthwise tolerance ± 2 mm
Thickness tolerance -1 ± 2 mm
Edge straightness ≤ 0,1%
Water absortion 0.20g / cm3
Water diffusion resistance µ:3,5

Values will vary according to different thicknesses. Some values quoted relate to internal testing across the size range. Individual test certificates are available upon request. We reserve the right to improve product performance at any time and without prior notice. Stricter board tolerances can be achieved to suit specific project requirements.


Download